SERVICE & SETUP MANUAL
BOILER
ELECTRONIC CONTROLLER
Riverside Hydronics, LLC • 3220 Galvez Ave • Fort Worth, Texas 76111 • 800-990-5918
Vue de la page 0
1 2 3 4 5 6 ... 23 24

Résumé du contenu

Page 1 - Page 1/ 24 34-81 10/2013

Page 1/ 24 34-81 10/2013 SERVICE & SETUP MANUAL BOILER ELECTRONIC CONTROLLER Riverside Hydronics, LLC • 3220 Galvez Ave •

Page 2 - Page 2/ 24 34-81 10/2013

Page 10/ 24 34-81 10/2013 5. PARAMETERS All the parameters can be set in: - Pr1: immediately accessible menu. - Pr2: password protected men

Page 3 - 2. WIRING DIAGRAMS

Page 11/ 24 34-81 10/2013 Label Firm Version Description Range X÷YFromXtoY Rev 0.3 Level Rev 0.5 Level Hex Modbus Address Base 0 Modbus Co

Page 4 - 3. DISPLAY AND INTERFACE

Page 12/ 24 34-81 10/2013 Label Firm Version Description Range X÷YFromXtoY Rev 0.3 Level Rev 0.5 Level Hex Modbus Address Base 0 Modbus Co

Page 5 - Page 5/ 24 34-81 10/2013

Page 13/ 24 34-81 10/2013 0.3 Probe3Information/StatusNormal=512or0x0200,Fault=515or0x0203.Faultwillbuz,FlashRedP3bit(0,1

Page 6 - Page 6/ 24 34-81 10/2013

Page 14/ 24 34-81 10/2013 6. RELAY OUTPUTS 6.1 OUTPUT SETUP AND SPECS 1. 3 relay outputs. SPST relay contacts going to spade terminals #4-

Page 7 - Page 7/ 24 34-81 10/2013

Page 15/ 24 34-81 10/2013 6.3 OUTPUT 2 2ND STAGE (oS2=Std 2on=rEG) Kind of action: Heating Reference probe: TP1 Terminals: SPADE 6 & 7 R

Page 8 - 4. PROGRAMMING

Page 16/ 24 34-81 10/2013 6.5 OUTPUT 3 TEMPERATURE PROTECTION (3on=rEG) Kind of action: Heating Reference probe: TP1 or TP2 Terminals: SPADE

Page 9 - Page 9/ 24 34-81 10/2013

Page 17/ 24 34-81 10/2013 6.6 OUTPUT 3 ALTERNATE SET POINT Kind of action: Heating Reference probe: TP1 or TP2 Related Parameters: St3, Hy3

Page 10 - 5. PARAMETERS

Page 18/ 24 34-81 10/2013 7. MODULATION OUTPUT Kind of action: if Sr< 0 Heating; if Sr>0 Cooling. See diagrams. Current(mA)Temper.204S

Page 11

Page 19/ 24 34-81 10/2013 8. MODULATION BUFFER Kind of action: Heating Reference probe: TP2 Related Parameters: Th4, HY4 NOTES 1. This f

Page 12

Page 2/ 24 34-81 10/2013 INDEX 1. TECHNICAL DATA _________________________________________________________________ 3 2. WIRING DIAGRAMS _____

Page 13

Page 20/ 24 34-81 10/2013 11. HOT KEY PROGRAMMING To upload program from control to HOT KEY: To download program from HOT KEY to control:

Page 14 - 6. RELAY OUTPUTS

Page 21/ 24 34-81 10/2013 12. ASSIGNING TEMPTRAC® ADDRESS FOR MODBUS RTU The first step to interfacing a BAS (Building Automation Control) wi

Page 15

Page 22/ 24 34-81 10/2013 13. ALARMS Alarm messages are displayed in the lower display of the TempTrac and are alternated with the default me

Page 16

Page 23/ 24 34-81 10/2013 13.1 DIGITAL INPUT ALARMS Digital Inputs Polarity of the inputs is determined by the i1p, i2p, i3p parameters. If

Page 17 - Alternate Set Point Control

Page 24/ 24 34-81 10/2013 13.3 ALARM RECOVERY 1. Probe alarms: “P1”, “P2”, and “P3”; automatically stop a few seconds after the probe retur

Page 18 - 7. MODULATION OUTPUT

Page 3/ 24 34-81 10/2013 1. TECHNICAL DATA Housing: Self-extinguishing ABS. Case: Facia 100x64 mm; depth 76mm Mounting: Panel mounting in a 5

Page 19 - 10. WARM WEATHER SHUT DOWN

Page 4/ 24 34-81 10/2013 3. DISPLAY AND INTERFACE 3.1 KEYBOARD SET - Displays and modifies the temperature set points. - In programmi

Page 20 - 11. HOT KEY PROGRAMMING

Page 5/ 24 34-81 10/2013 KEY COMBINATIONS + To lock and unlock the keyboard. + To enter the programming mode. + To exit the progra

Page 21

Page 6/ 24 34-81 10/2013 3.3 UPPER LED READOUT (RED) The default display of this readout is the temperature sensed at Probe 2, which is gene

Page 22 - 13. ALARMS

Page 7/ 24 34-81 10/2013 3.6 TO SET THE ENERGY SAVINGS TIME 1. Push the button for more than 3 seconds and the first parameter of the ener

Page 23

Page 8/ 24 34-81 10/2013 4. PROGRAMMING 4.1 SET POINTS PROGRAMMING 1. Push the key, the upper display will show the “St1”, while the lower

Page 24 - 800-990-5918

Page 9/ 24 34-81 10/2013 4.4 HOW TO CHANGE THE PARAMETER VALUES IN “Pr2” 1. Enter the Programming mode. 2. Select the required parameter wi