Riverside Hydronics ProtoNode Spécifications Page 11

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 25
  • Table des matières
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 10
Riverside Hydronics
®
, LLC – 34-160 10/11
990 Haltom Road - Fort Worth, Texas 76117 - Tel 1-800-990-5918 Page | 11
The TIER 1 SYSTEM STATUS screen is provided to monitor the most commonly need system
informationformultipleboiler.Thefirstscreendisplaythisinformationforuptoeightboileranda
supplementalscreenTIER 1912displaysthesameinformationforboilers9to12.
SYSTEM
TEMPdisplaysthecurrentsystemtemperature.
OUTDOOR TEMP displays the
currentsystemtemperature.
ADJUSTED SETPOINT displays the
set point after a reset function
such as Outdoor Reset, Scheduled
Setbackor Remot eSetpoint
adjustment have been made. This
is the same parameter as is
locatedontheTier1menu.
SETPOINT is the current
set point
foreachboilerinthesystem.
INLETthisisthecurrentmeasuredreturnwatertemperatureofeachboiler inthesystem.
OUTLETthisisthecurrentmeasuredsupplywatertemperatureofeachboilerinthesystem.
The OUTLET temperature displays can be turned off when not used
as shown here by
touchingthedisplay.
Thenumericaldisplayboxeslocatedatthebottomofthescreenindicatedthetimeelapsed
asthe controlcountsuptoenabletherespectiveboiler (top)or downtodisable (bottom).
ThetotaltimeisenteredonOPTIONSCREEN1.
Thereis
aTIER2SYSTEMSTATUSscreenwhichprovidesthesameinformationfortheTier2boilers
withaddressesfrom13to20.
TIER 1 SYSTEM S
T
ATU
S
Vue de la page 10
1 2 ... 6 7 8 9 10 11 12 13 14 15 16 ... 24 25

Commentaires sur ces manuels

Pas de commentaire